IEEE-RTS-24

来源:伴沃教育
TheIEEEReliabilityTestSystem

1SystemDescription

The24bussystem[1]isillustratedinFigure1.Theslackbusofthesystemisnode13.

Figure1:24-buspowersystem–IEEEOneAreaRTS-96

1

1.1UnitData

Tables1-3presentthegeneratingunits’dataofthepowersystem.Thegeneratingunitsofferasingleblockofenergy,upanddownreservecapacity.Table1providesthetechnicaldataofgeneratingunits,Table2categorizestheunitsindifferenttypesandTable3providesthecostsandinitialstateofthegeneratingunitsatthebeginningoftheschedulinghorizon.Thedataisbasedon[1],[2],[3].

Table1:TechnicalDataofGeneratingUnitsPmaxPminR+R−RURDMWMWMWMWMW/minMW/min40040015215215515531035035059160300

10010030.430.454.2554.25108.514075206.8512300

0040403030604070180600

0040403030604070180600

6.676.672233347315

6.676.672233347315

UnitUnit18Unit21Unit1Unit2Unit15bUnit16Unit23aUnit23bUnit7Unit13Unit15aUnit22

Node182112151623237131522

UTh1188888881240

DTh1144888881020

Table2:UnitTypeUnitTypeUnit(s)NuclearCoal/StreamCoal/3StreamOil/StreamHydro

182112151623a

23b7131522

Table3:CostsandInitialStateofGeneratingUnitsUnitCCuCdCsuPiniUini

$/MWh$/MW$/MW$MW0/1Unit18

Unit21Unit1Unit2Unit15bUnit16Unit23aUnit23bUnit7Unit13Unit15aUnit22

5.475.4713.3213.3210.5210.5210.5210.8920.7020.9326.110.00

0015151616171610870

001414141416149750

001430.41430.4312312624229817253056.74370

320320121.6121.60124248280000240

111101110001

Tinih50162222-2101050-2-1-124

2

ApositiveTinishowsthetimeperiodsthatthegeneratingunithasbeenonlineatthebeginningofschedulinghorizon.Anegativeoneshowsthetimeperiodsthatthegeneratingunithasbeenofflineatthebeginningofschedulinghorizon.

1.2LoadData

InFigure2,theloadprofileisillustrated.Table4providesthetotalsystemdemandperhourandTable5presentsthenodelocationoftheloads,aswellasloadateachnodeasapercentageofthetotalsystemdemand.Theloaddataisbasedon[2].

System Demand30002500System Demand [MW]2000150010005000510Hours1520Figure2:SystemDemandProfile

Hour123456789101112

Table4:LoadProfileSystemDemandHourSystemDemand

MWMW

1598.2521502.8341431.2701407.4161407.4161431.2701765.2332051.4872266.1782290.0322290.0322266.178

131415161718192021222324

2266.1782266.1782218.4692218.4692361.5962385.4502385.4502290.0322170.7601979.9241741.3791502.834

3

Table5:NodeLocationandDistributionoftheTotalSystemDemandLoadNode%ofsystemloadLoadNode%ofsystemloadLoadLoadLoadLoadLoadLoadLoadLoadLoad

123456789

123456789

3.83.46.32.62.54.84.466.1

LoadLoadLoadLoadLoadLoadLoadLoad

1013141516181920

1013141516181920

6.89.36.811.13.511.76.44.5

1.3TransmissionLines

ThetransmissionlinesdataisgiveninTable6.Thelinesarecharacterizedbythenodesthatareconnected,aswellasthereactanceandthecapacityofeachline.Thedataisbasedon[2].

Table6:ReactanceandCapacityofTransmissionLines

ToReactanceCapacityFromToReactanceCapacity

p.u.MVAp.u.MVA2

354692491010891011121112

0.01460.22530.09070.13560.2050.12710.0840.1110.0940.06420.06520.17620.17620.0840.0840.0840.084

175175350175175175400175350175350175175400400400400

1111121213141515151616171718192021

1314132323161621241719182221202322

0.04880.04260.04880.09850.08840.05940.01720.02490.05290.02630.02340.01430.10690.01320.02030.01120.0692

5005005005005005005001000500500500500500100010001000500

From1112233456788991010

2ImplementationIncludingWindPowerProduction

Itisrecommendedtoincludesixwindfarmsatdifferentlocationsthroughoutthegrid.Itisproposedtolocatethewindfarmsat3,5,7,16,21and23nodes.Inthiscase,thecapacityonthetransmissionlinesconnectingthenodepairs(15,21),(14,16)and(13,23)isreducedto400MW,250MWand250MW,respectively.Thisisdoneinordertointroducebottlenecksinthetransmissionsystem.

4

References

[1]C.Grigg,P.Wong,P.Albrecht,R.Allan,M.Bhavaraju,R.Billinton,Q.Chen,C.Fong,S.

Haddad,S.Kuruganty,etal.TheIEEEReliabilityTestSystem1996.Areportpreparedbythereliabilitytestsystemtaskforceoftheapplicationofprobabilitymethodssubcommittee.IEEETransactionsonPowerSystems,14(3):1010-1020,1999.[2]A.J.Conejo,M.Carrion,J.M.Morales.DecisionMakingunderUncertaintyinElectricity

Markets.SpringerUS,2010.[3]F.Bouffard,F.D.Galiana,A.J.Conejo.Market-ClearingwithStochasticSecurityPartII:

CaseStudies.IEEETransactionsonPowerSystems,20(4):1827-1835,2005.

Nomenclature

CCdCsuCuDTPiniPmaxPminR+R−RDRUTiniUiniUT

ProductioncostDownwardreservecostStartupcostUpwardreservecost

MinimumdowntimeofeachgeneratingunitPoweroutputofeachgeneratingunitattime0MaximumoutputpowerofeachgeneratingunitMinimumoutputpowerofeachgeneratingunit

MaximumreservecapacityofupregulationofeachgeneratingunitMinimumreservecapacityofupregulationofeachgeneratingunitRampdownrateofeachgeneratingunitRampuprateofeachgeneratingunit

Numberofhoursofwhichthegeneratingunitwasin/outatthebeginningofplanninghorizonStatingwhethertheunitisonline/offlineattime0Minimumuptimeofeachgeneratingunit

5